Heat transfer through a box beam from an impinging hydrogen flame

Blaylock, Myra L.; Schroeder, Benjamin B.; Lafleur, Chris; Bran Anleu, Gabriela A.

An analysis was performed to determine whether a hydrogen jet flame impinging on a tunnel ceiling composed of multiple prestressed steel reinforced concrete box beams could result in permanent damage to the tunnel. The lower layer of the concrete box beam was modeled to determine whether heat reaches the steel reinforcing bars and whether spalling could occur. Heat transfer analysis shows that the temperature remains constant at the location of the steel reinforcing bars after 1.3 minutes of impingement and reaches a maximum of 130°C after 5 minutes. However, assuming a constant impingement for 5 minutes is an over estimation due the existing fire model which includes conservative assumptions. Explosive spalling may occur at a thin layer (~0.05 in. at 50 seconds, 0.1 in. at 5 minutes) at the bottom surface of the concrete box beam, but the steel reinforcing bars will not be exposed to the hydrogen flame.