Baird, Austin R.; Herrera, Joshua M.; Muna, Alice B.

The intent of the Building Fire Consequence Index (BFCI) at Sandia National Laboratories (SNL) is to provide a method to rank buildings based on the consequence of a fire in that building. This indexing tool will be used to determine the frequency a building's fire protection assessment (FPA) will be performed. Per DOE O 420.1C Chg. 1, Facility Safety, a FPA must be conducted annually (for facilities with a replacement value in excess of $100 million, facilities considered a high hazard, or those in which vital programs are involved), every three years (for remaining low and ordinary hazard facilities), or at a frequency with appropriate justification approved by the Depaitinent of Energy (DOE) head of field element. The BFCI provides a method for a graded approach utilizing a scoring criteria for various categories such as replacement plant value, building content value, hazards, mission dependency index, etc. when assigning FPA frequencies1.