Publications Details
ESD hazards associated with CO{sub 2} refrigeration
Jones, R.D.; Chen, K.C.; Holmes, S.W.
Apparent malfunctions of two Trajectory Sensing Signal Generators (TSSGs) were observed during B61-3/4/10 trajectory arming tests at the Pantex Weapons Evaluation Test Laboratory (WETL). On two subsequent occasions, the TSSG used in the B83 bomb developed single-channel failures during tests at WETL. It was concluded that the failures were related to the electrostatic discharge (ESD) hazard associated with the use of a Thermotron{reg_sign} liquid carbon dioxide (CO{sub 2}) refrigeration system. It was demonstrated that during temperature conditioning, the case of the TSSG can acquire a substantial electrostatic charge as a result of triboelectric processes. A series of tests was performed to identify the charging mechanisms associated with liquid CO{sub 2} refrigeration systems and a quantitative assessment of the ESD hazard was made. The conclusions and recommendations derived in these tests were summarized in a Significant Finding Investigations Closeout. The purpose of this report is to provide formal documentation for, and elaboration on, issues addressed in the Findings.