An investigation of the effects of thermal aging on the fire damageability of electric cables

Nowlen, Steven P.

This report documents the findings of an experimental investigation of the effects of thermal aging on the fire damageability of electric cables. Two popular types of nuclear qualified cables were evaluated. For each cable type, both unaged (i.e., new off the reel) and thermally aged samples were exposed to steady-state elevated temperature environments until conductor-to-conductor electrical shorting was observed. Plots of the time to electrical failure versus the exposure temperature were developed and thermal damage thresholds were determined. For one cable type, the thermally aged cables were less vulnerable to thermal damage than were the unaged samples as demonstrated by an increase in the thermal damage threshold for the aged samples, and an extended survival time at exposure temperatures above the damage threshold for aged samples compared to unaged samples. For the second cable, the threshold of thermal damage was lowered somewhat by the aging process, an indication of an increased vulnerability to thermal damage due to aging. However, for the higher temperature exposures, no statistical difference between the damage times for aged and unaged cable samples was noted. For both cable types, the changes in the thermal damage threshold observed were not considered significant in terms of fire risk. 4 refs., 9 figs., 8 tabs.

More Details

The Impact of Thermal Aging on the Flammability of Electric Cables

Nowlen, Steven P.

An investigation of the impact of thermal aging on the flammability of two common types of nuclear grade electrical cables has been performed. Four large-scale flammability tests were performed with each of the two cable types tested in both an unaged (i.e., new off the reel) and a thermally aged (artificially aged) condition. In all cases, the fire was observed to consume virtually all of the combustible cable jacket and insulation material present. However, for both cable types tested, the thermal aging process caused a decrease in the cable flammability as demonstrated by decreases in the rate of fire growth, peak fire intensity, total heat released and near fire temperatures. This result is consistent with past cable aging studies because it has been observed that the thermal aging process will drive off certain of the more volatile constituents of a polymeric material. Presumably, when these aged materials are subjected to a fire, the evolution of volatile combustible gases is reduced as compared to the unaged materials, and hence, flammability is reduced. The results of these tests indicate that, at least for the two cable types tested, the evaluation of cable flammability using unaged cable samples will remain a conservative indicator of cable flammability in a thermally aged condition.

More Details

A summary of nuclear power plant fire safety research at Sandia National Laboratories 1975-1987

Nowlen, Steven P.

This report summarizes the results and conclusions generated by the US Nuclear Regulatory Commission sponsored Fire Protection Research Program at Sandia National Laboratories. Efforts conducted from the programs inception in 1975 through 1987 are discussed. The individual efforts are discussed within a framework based on specific areas of investigation. Early efforts are presented in the context of investigations of specific regulatory concerns. Later efforts are presented within the context of an integrated investigation of fire safety issues. This integrated approach considers the fire safety issue in terms of (1) source fire characterization, (2) detection and suppression system effectiveness, (3) room effects, (4) equipment response, and (5) room-to-room fire effects. The report provides a complete bibliography of reports and journal articles generated as a result of these efforts with a cross-reference listing of major reports to specific efforts. 98 refs., 23 figs., 20 tabs.

More Details

Nuclear power plants: A unique challenge to fire safety

Nowlen, Steven P.

Nuclear power plants present the fire protection community with unique challenges. In addition to the traditional concerns of life safety and property loss prevention, nuclear safety analysts must also be concerned with the impact of fires on the safe operability of the nuclear reactor. Safe shutdown equipment must be protected from fire damage. When nuclear power plants were first designed and built, fire safety considerations were based primarily on the same criteria applied to general industrial facilities, primarily those concerning life safety and property loss prevention. This practice continued until 1975 when the Brown's Ferry nuclear reactor site experienced a severe cable tray fire. The fire burned for over seven hours, due in part to the reluctance of on-site personnel to use water on the fire for fear of shorting out critical electrical circuits. 4 figs.

More Details

An overview of the fire risk scoping study

Nowlen, Steven P.

The fire risk scoping study was sponsored by the US Nuclear Regulatory Commission and performed at Sandia National Laboratories. The study was initiated as a result of previous USNRC-sponsored fire research efforts that had identified certain fire risk issues that had not been addressed in previously completed commercial nuclear power plant fire risk analyses. The specific objectives of this study were: (1) to review and requantify fire risk scenarios from four fire probabilistic risk assessments in light of updated data bases made available as a result of USNRC-sponsored Fire Protection Research Program and updated computer fire modeling capabilities, (2) to identify potentially significant fire risk issues that have not been previously addressed in a fire risk context and to quantify the potential impact of those identified fire risk issues where possible, and (3) to review current fire regulations and plant implementation practices for relevance to the identified unaddressed fire risk issues. 9 refs., 3 tabs.