Detection of localized cable damage using a preionized gas technique. Final report
Vigil, R.A.; Jacobus, M.J.; Bustard, L.
Because of the absence of a nearby, well-defined ground plane, performing electrical tests on unshielded cables installed in conduits is difficult. Experiments were run to develop a preionized gas troubleshooting technique to detect localized degradation of unshielded cables in conduits. This was achieved by introducing a readily ionizable gas like helium (or argon) in the conduit air space and then applying a moderately high voltage to the test cable, thus ionizing the gas surrounding the cable. Breakdown testing was performed on various types of damaged and undamaged cables. Other parameters necessary for practical implementation of the technique were also examined, including gas type, position of the cable with respect to the conduit wall, length of cable, conduit configuration, conduit size, and gas propagation in conduits. High potential testing of cables in the presence of preionized helium gas provides essentially the same information as high potential testing in water. A test criterion of 30 kVdc or 10 kVac would detect when 5-mils of insulation remain on one particular tested cable. No undamaged cable was noted to break down at these voltages. A high concentration of helium is required to perform the test, but this is easily attained with straightforward preparations. A cable with through-wall damage can easily be detected with a test criterion of approximately 1.5 kvac.